UPS EVO DSP PLUS TT
Messages on the LCD
Explanation
Fault! Over Temperature
High Temperature: make sure adequate space is allowed for air
ventilation and the fan is working
Fault! CAN Fault
CAN communication fault
Fault! TRIG0 Fault
Synchronized trigger signal fault
Fault! Relay Fault
Inverter relay fault
Fault! Line SCR Fail
Line SCR short circuit fault
Fault! EEPROM Fault
EEPROM operation error
Fault! Parallel Cable Loosen Fault
As stated
Fault! DSP MCU Stop Communicate
As stated
Fault! Bypass Temperature Fault
As stated
Fault! Bypass SCR Fault
As stated
Line Fail
Utility lost or abnormal
Line Restore
Utility recovered to normal
Warning! EPO Active
Check the EPO connector
Warning! Over Load Fail
The load devices are demanding more power than the UPS can
supply. Line Mode will transfer to Bypass mode
Warning! Communicate CAN Fail
CAN communication error
Warning! Over Load
In Line mode, the load devices are demanding more power than
the UPS can supply
Warning! Battery Open
Battery not connected
Warning! Battery voltage High
Battery voltage is too high
Warning! Turn On Abnormal
As stated
Warning! Charge Fail
As stated
Warning! EEPROM Fail
EEPROM operation error
Warning! Fan Lock
As stated
Warning! Line Phase Error
As stated
Warning! Bypass Phase Error
As stated
Warning! N Loss
Neutral loss
Warning! Internal Initial Fail
As stated
Warning! Comm Syn Signal Fail
Communicate synchronization signal fail
Warning! Comm. TRIG0 Fail
Communicate trigger signal fault
Warning! Power Stage loss
Power stage is not detected
Warning! Parallel Sys Config. Wrong
Parallel system configuration error
Warning! Maintenance Bypass
Enter maintenance bypass status
Warning! Battery Age Alert
Battery life expiration
Warning! Parallel UPS Cable Loosen
As stated
Warning! Parallel UPS Config. Wrong
Parallel UPS configuration error
Warning! Battery Voltage Low
Battery voltage is too low
Warning! ID Conflict
Power stage/module ID in conflict
Pre-Alarm! Line Voltage Fail
Line voltage over range
Pre-Alarm! Line Voltage Normal
Line voltage recovered to normal
Pre-Alarm! Line Frequency Unstable
Line frequency over range
Pre-Alarm! Line Frequency Normal
Line frequency recovered to normal
Pre-Alarm! Over Load
Output Load over range
Pre-Alarm! Load Normal
Output Load recovered to normal
Pre-Alarm! Load Unbalance
Output Load unbalance