ENGLISH
UPS EVO DSP PLUS TT
27
User’s manual
Table 5-10: Setup-Pre-Alarm Setting List
Setting Item
Sub Item
Explanation
Line Voltage
Range
--
Set Line Voltage Range.
Upper limit:
+5%
+10%
+15%
+20 (Default)
Lower limit:
-5%
-10%
-15%
-20 (Default)
Line
Frequency
Range
--
Set Line Frequency Range.
Upper / Lower limit:
+/- 1Hz
+/- 2Hz
+/- 3 Hz
+/- 4Hz (Default)
Load
--
Set UPS Overload Percentage (40~100%):
20% (Default)
Set UPS Load Unbalanced Percentage (20~100%):
100% (Default)
5.2.5.5
Setup Parallel Screen
The Parallel Screen and Setting options are shown in figure 5.18; refer to table 5-11.
.
Figure 5.18 - Setup Parallel Screen
Table 5-11: Setup-Pre-Alarm Setting List
Setting Item
Sub Item
Explanation
UPS Parallel
--
Set UPS Parallel:
Disable (Default)
Enable
Indipendent
Battery
--
Set Indipendent Battery:
Disable (Default)
Enable