![Technoware EVO DSP PLUS TT 100 KVA User Manual Download Page 42](http://html1.mh-extra.com/html/technoware/evo-dsp-plus-tt-100-kva/evo-dsp-plus-tt-100-kva_user-manual_1070751042.webp)
ENGLISH
User’s manual
36
UPS EVO DSP PLUS TT
6
ELECTRICAL INSTALLATION
6.1
Front Side
Each UPS comes equipped with a front door key. After opening the front door, you will see communication area
and several power stages/modules inside.
6.1.1
Power Stage/Module
EVO DSP PLUS TT has an advanced architecture composed of some power stage/modules (from 3 to 6). Each
power stage/module includes a power factor correction Rectifier, a Battery Charger, an Inverter and a Control
Circuits.
There are three DIP SWITCHES (see #2- figure 6.1) for power stage/module ID address setting.
In the same
cabinet, each power stage/module ID address MUST be exclusive
. Please refer to table 6.1. where the ID
addresses assigned to the power stages/modules are indicated
Figure 6.1 - Power Stage/Module
No.
Item
Description
FAN
Air enters the power stage/module through the front grills and exhausted through
rear of the module. Please do not block the ventilation vent port.
DIP SWITCHES
There are three DIP SWITCHES for power stage/module address setting. In the
same cabinet, each power stage/module ID MUST be exclusive. Please refer to
table 6.1.
BATTERY START
BUTTON
When AC input is not existing, use this button to start battery power for UPS.
FAULT LED
ON
The power stage/module is in fault condition.
ON/OFF 0.5 sec
The power stage/module IDs in conflict.
RUN LED
ON
The power stage/module normally works as a SLAVE unit.
ON/OFF 0.5 sec
The power stage/module normally works as a MASTER unit.
ON/OFF 0.15 sec
The CAN BUS communication doesn’t work.