ENGLISH
UPS EVO DSP PLUS TT
59
User’s manual
8
Technical Characteristics
UPS EVO DSP PLUS TT Model
100
120
160
200
Power
100 KVA
120 KVA
160 KVA
200 KVA
Nominal Active Power
90 KW
108 KW
144 KW
180 KW
Power Factor
0.9
Technology
On-Line Double Conversion Transformerless (VFI-SS-111)
Dimension (W x H x D) mm
945 x 567 x 1015
995 x 567 x 1455
Net Weigt (Kg)
197
232
309
343
INPUT
Phases
3 Phases with N Ground
Nominal Voltage (Phase-Phase)
380 / 400 / 415 Vac (selectable)
Nominal Voltage (Phase-Neutral)
220 / 230 / 240 Vac (selectable)
Voltage Range
Line Mode
Full Load
305V ~ 478V (176V ~ 276V Phase-Phase)
70% Load (De-rating)
208V ~ 478V (120V ~ 276V Phase-Phase)
Nominal Frequency
50/60 Hz (Auto-selectable)
Frequency Range (Line mode)
40Hz ~ 70Hz
Synchronized Range
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz) User Programmable
Total Harmonic Distortion Input (THDi)
< 3% (at 100% Load with Linear Load)
Input Power Factor
≥ 0.99 (at 100% Load)
OUTPUT
Phases
3 Phases with N Ground
Nominal Voltage (Phase-Phase)
380 / 400 / 415 Vac (selectable)
Nominal Voltage (Phase-Neutral)
220 / 230 / 240 Vac (selectable)
Voltage Regulation
< 1% Typical (Balanced Load); < 2% Typical (Unbalanced Load)
Inverter Waveform
True Sinewave
Nominal Frequency
50/60 Hz (selectable)
Frequency Range (Synchronized Range)
40Hz ~ 70Hz
Frequency Range (Battery mode)
(50 Hz ± 0.1%) or (60 Hz ± 0.1%)
Total Harmonic Distortion (THD)
< 2% (100% Linear Load); < 4% (100% Non-Linear Load)
Crest Factor
3:1 max
Overload (Line mode)
1 hour for 105 ~110%, 10 mins for 111~125%, 1 min for 126~150%, 200ms for >150%
Overload (Battery mode)
1 hour for 105 ~110%, 10 mins for 111~125%, 1 min for 126~150%, 200ms for >150%
Transfer Time
(Line <--> Battery)
0 ms
(Battery <--> Bypass)
0 ms
(Line <--> Eco)
< 10 ms