UPS EVO DSP PLUS TT
Table 5-8: Setup-System Setting List
Setting Item
Sub Item
Explanation
Output
Voltage
--
Set Output Voltage:
220Vac (Default)
230Vac
240Vac
Bypass Setting
Bypass Voltage
Range
Set Bypass Voltage Range.
Upper limit:
+10%
+15% (Default)
+20%
Lower limit:
-10%
-20% (Default)
-30%
Bypass
Frequency
Range
Set bypass Frequency range.
Upper/ Lower limit:
+/- 1Hz
+/- 2Hz
+/- 4Hz (Default)
Converter
Mode
--
Set Converter Mode:
Disable (Default)
Enable
ECO Mode
--
Set ECO Mode:
Disable (Default)
Enable
Bypass Mode
--
Set Bypass Mode:
Disable (Default)
Enable
If you need the Bypass power when UPS is OFF, please enable it.
Auto-Restart
--
Set Auto-Restart:
Disable
Enable (Default)
After “Enable” is set, once UPS shutdown occurs due to low battery and
then utility restores, the UPS will return to Line Mode.
Cold Start
--
Set Cold Start:
Disable
Enable (Default)
After “Enable” is set, the UPS can be turned on without connecting to
utility by pressing BATTERY START Button. Refer to section 7.2 “Cold
Start Startup” for the details.
Battery Mode
Delay Time
--
Set System Shutdown Delay Time in Battery Mode (0~9990 sec):
0: Disable (Default)
NOT 0: Enable
When this feature is enabled, UPS will shut off output after UPS operates
in Battery Mode for certain seconds.
Shutdown/
Restore
System
Shutdown Time
Set System Shutdown Time (0.2~99 min):
0.2 min (Default)
This delay time will start counting when the CONTROL-Shutdown
command is executed.
System Restore
Time
Set System Restore Time (0~9999 min)
1 min (Default)
This delay time will start counting after shutdown time is elapsed when
the CONTROL-Shutdown Restore command is executed.
Charger Test
--
Set Charger Test:
Disable (Default)
Enable