ENGLISH
User’s manual
60
UPS EVO DSP PLUS TT
MAINS BYPASS (BYPASS)
Phases
3 Phases with N Ground
Nominal Voltage (Phase-Phase)
380 / 400 / 415 Vac (selectable)
Nominal Voltage (Phase-Neutral)
220 / 230 / 240 Vac (selectable)
Voltage Range
Upper Limit
+10% / +15% / +20%; default: +15%
Lower Limit
-10% / -20% / -30%; default: -20%
Nominal Frequency
50Hz/60Hz (Auto-selectable)
Frequency Range
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz)
Synchronized Range
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz) User Programmable
EFFICIENCY
Line Mode
94%
BATTERIES (only inside External battery Box)
Battery Type
Lead acid, sealed, free maintenance – 12 Vdc
Number of Batteries
2 x (16+16) - (inside External Battery Box)
Nominal Battery Voltage
± 192 Vdc (total 384 Vdc)
Battery Charge Time (typical)
6-8 hours
ENVIRONMENTAL CONDITIONS
Storage Temperature Range
-25°C to +55°C (-15°C to 40°C recommended for longer Battery life)
Operating Temperature Range
0°C to +40°C (20°C to 25°C recommended for longer Battery life)
Relative Humidity Range
0% - 95% (not condensing)
Max. Altitude
3000 m
Protection level
IP 20
Cooling
Fan cooling
Audible Noise (at 1 meter)
< 70 dBA
STANDARDS
Safety
Low Voltage (Safety) Directive 2014/35/EU
Performance
IEC 62040-3
EMC
EMC (Electro-Magnetic Compatibility) Directive 2014/30/EU - category C3
Product certification
CE
COMMUNICATIONS
Computer Interface
1 RS232 port and 1 USB port
Software
Included UPS Management Software,
compatible with: Windows, Linux, Unix, etc.
SNMP Interface
Optional
OTHERS
EPO (Emergency Power OFF)
Included
Dry Contact Interface
Optional
Manual Bypass for Maintenance
Included
Parallel Operating Mode
Optional (up to 2 UPS)
ECO Mode
Selectable
Frequency Converter Mode
Selectable
Technical data may change without prior notice