UPS EVO DSP PLUS TT
7.3.3
Turn OFF Operation in Battery Mode
The LCD diagram is shown below when the UPS operates in the Battery Mode.
Please follow below step.
1.
Press Power On/Off Button for 2 seconds
to turn OFF the UPS or
use the Menu-Control-System Turn Off
to
turn OFF the UPS
7.4
Maintenance Bypass (Manual Bypass) Operation
If any fault occurs on any one of power stages/modules, please follow below steps to transfer to Maintenance
Bypass for maintenance.
Maintenance and service may only be performed by authorized technical personnel.
The procedure of switching into Maintenance Bypass shall only be executed by
authorized technical service personnel.
During Maintenance Bypass operation, loads are fed directly from Bypass mains.
Therefore no protection against mains disturbances or interruptions is present..