36
Configuration
>... >
Analog inputs
>
Supply air
temperature
2021–03–01
Name
Supply air temperature
Original name
Supply air temperature
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
I/O allocation settings
3. Select the submenu related to the I/O to rename (e.g
Analog inputs
if temperature sensor)
4. Select the I/O function of which to rename (e.g
Supply air temperature
)
5. Edit the name of the I/O (in-/outputs) by selecting
Name
.
14.4.1.3 Sequence naming
Change the name of a heating/cooling sequence by selecting the desired sequence in the
Configuration
>
Func-
tions
>
Function activation
>
Heating/Cooling sequence setup
menu and changing the menu row
Name
.
Configuration
> ... > ... >
Heating/Cooling sequence
setup
2021–03–01
Position
Heating
Cooling
Start
Heating
Start
Cooling
Name
SEQ-H
Off
3
0 %
0 %
Cooling 2
>
Configuration
>... >
Heating/Cooling sequence setup
>
Cooling 2
2021–03–01
Name
Cooling 2
Original name
Cooling 2
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Functions
3. Select
Function activation
4. Select
Heating/Cooling sequence setup
5. Select the sequence to rename (e.g
Cooling 2
)
6. Edit the name of the sequence by selecting
Name
.
14.4.1.4 Alarm naming
How to edit alarm names is described in chapter 14.4.2.
254051 | A001