14.4.8.2 Configuration
Configure the operation of the air handling unit, outdoor/exhaust air dampers, the fan setpoints and fire damper func-
tion when Fire alarm in the
Configuration
>
Functions
>
Fire/Smoke > Fire function
submenus.
Overview:
Configuration
> ... >
Fire/Smoke
>
Fire function
2021–03–01
Operation mode when fire alarm
Continuous run
Supply air fan setpoint type when fire alarm
Manual output
Manual output
75%
Extract air fan setpoint type when fire alarm
Manual output
Manual output
75%
Outdoor air damper function when fire alarm
Normal function (follow the
fan)
Exhaust air damper function when fire alarm
Normal function (follow the
fan)
Configuration
> ... >
Fire function
>
Fire damper
2021–03–01
Mode
Not active
Test
No test
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Functions
3. Select
Fire/Smoke
4. Select
Fire function
5. Select desired air handling unit’s operation when fire alarm as
Mode
6. Select desired fan setpoint type as
Supply air fan setpoint type when fire alarm
7. Select desired fan setpoint type as
Extract air fan setpoint type when fire alarm
8. If either
Manual setpoint
or
Manual output
was selected set the desired value in the corresponding menu row
now visible
9. Select the operation of the outdoor/exhaust air damper when fire alarm as
Outdoor/Exhaust air damper when
fire alarm
10.Select
Fire damper
11.Select the normal position of the fire dampers or if fire damper function should not be used as
Mode
12.Select if and how the fire dampers shall be tested as
Test
.