34
14.2.1.3 Allocation
Configuration
>
Configuration wizard
>
Set up
“function” >
In-/Outputs
Confirm the in-/output allocation of the connected signals and sensors. Configure in-/output settings (sensor measuring
range, polarity, edit name of sensor/signal etc.) as necessary. Complete the setup by pressing
Confirm In-/Outputs
and complete setup
.
Configuration
> ... >
Set cooler
>
In-/Outputs
2021–03–01
Analog outputs
Range output
Device
Position
Cooling (SEQ-C)
0–10V
Controller
AO2
Digital outputs
Contact function
Device
Position
Cooling pump (SEQ-C)
Normally open
Controller
DO3
Digital Inputs
Contact function
Device
Position
Feedback cooling (SEQ-C)
Normally open
Controller
DI5
Confirm In-/Outputs and complete setup
>
14.2.1.4 Completing the configuration wizard
A completed setup is listed as
Configured
in the configuration wizard menu. To make changes to an already config-
ured function, rerun the wizard or use the configuration menus described in chapter 14.4.
Configuration
>
Configuration wizard
2021–03–01
Set up pressure control
>
Set up cooler
Configured
>
Set up changeover
>
Exit to configuration menu
>
Complete configuration wizard
>
Select
Complete configuration wizard
once the desired setups have been completed. The configuration wizard
is still accessible from the configuration menu.
14.2.1.5 Operation settings
Note that functions configured via the wizard still require adaptation of its operation settings. These settings are found
in the functions submenu of
Data & Settings
as described in chapter 14.4.
14.3 Save commissioning settings
When the installation is complete and all functions are tested it is recommended to save a local backup of the current
configuration in the control unit.
Select
Yes
on
Save commissioning settings
in the
Configuration
>
System settings
>
Save and restore
settings
menu.
Overview:
Configuration
>
System settings
>
Save and restore
settings
2021–03–01
Save commissioning settings
Yes
Step by step:
254051 | A001