14.4.10.4 Operation settings
Adjust the start/stop point for the digital output:
Cooling start (SEQ-C)
in the
Data & Settings
>
Temperature
control
>
Cooling
menu.
Overview:
Data & Settings
>
Temperature control
>
Cooling
2021–03–01
Digital start output start point
10 %
Digital start output stop point
1 %
Data & Settings
>
Temperature control
>
Supply air
controller
2021–03–01
Min limit supply air
14 °C
Max limit supply air
30 °C
Reduction of min limit supply air if active DX-cooling
5 °C
Step by step:
1.
Select Data & Settings
from the navigation icons
2. Select
Temperature control
3. Select
Cooling
4. Set the desired output % to activate the digital output as
Digital start output start point
5. Set the desired output % to deactivate the digital output as
Digital start output stop point
6. Go back to
Temperature control
(use the navigation path
Data & Settings
>
Temperature control
)
7. Select
Supply air controller
8. Adjust the min. allowed supply air temperature when DX-Cooling is active as
Reduction of min limit supply
air if active DX-cooling
.