14.4.7.3 Allocation
Select I/O (in-output) placement for where the CO2 sensor is connected to the controller in the
Configuration
>
I/
O allocation settings
>
Analog inputs
menu.
Overview:
Configuration
>
I/O allocation settings
>
Analog
inputs
2021–03–01
Analog inputs
Device
Position
CO2 room/extract air
Controller
UI3
Configuration
> ... >
Analog inputs
>
CO2 room/extract air
2021–03–01
Min volt input (Vmin)
0.0 V
Man volt input (Vmax)
10.0 V
Sensor value at Vmin
0.0
Sensor value at Vmax
2000.0
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
I/O allocation settings
3. Select
Analog inputs
4. Select the input connected to the sensor (e.g. UI3) as position for
CO2 room/extract air
5. Select
CO2 room/extract air
6. Set
Sensor value at Vmin
the same as the start point of the sensor’s selected measuring range
7. Set
Sensor value at Vmax
the same as the end point of the sensor’s selected measuring range
8. Set
Min volt input (Vmin)
and
Max volt input (Vmax)
to values corresponding to the sensor’s signal type (e.
g. 0…10 V, 2…10 V etc.)