14.4.8.4 Operation settings
Set up the Fire damper test settings in the
Data & Settings
>
Fire/Smoke
menu.
Note:
Only applicable if fire damper test is configured.
Overview:
Data & Settings
>
Fire/Smoke
2021–03–01
Run time fire damper
90 s
Test interval fire damper
7 days
Test hour fire damper
15
Step by step:
1.
Select Data & Settings
from the navigation icons
2. Select
Fire/Smoke
3. Set max allowed fire damper run time as
Run time fire damper
4. Set day interval between fire damper tests as
Test interval fire damper
5. Select hour (1-24) for start of fire damper test as
Test hour fire damper
, e.g 15 means the fire damper test will
initiate at 3 pm (15:00) on test day.
14.4.9
Free cooling
14.4.9.1 Activation
Select
Yes
as
Free Cooling
from the list of available functions in the
Configuration
>
Functions
>
Function
activation
menu.
Overview:
Configuration
>
Functions
>
Function activation
2021–03–01
Free cooling
Yes
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Functions
3. Select
Function activation
4. Select
Yes
as
Free cooling