14.4.10 External cooler (DX)
14.4.10.1 Activation
Select and activate an unused cooling sequence (C, H or J) in the
Configuration
>
Functions
>
Function acti-
vation
>
Heating/Cooling sequence setup
menu.
Overview:
Configuration
> ... > ... >
Heating/Cooling sequence
setup
2021–03–01
Position
Heating
Cooling
Start
Heating
Start
Cooling
Name
SEQ-C
Off
2
0 %
0 %
Cooling
>
SEQ-H
Off
3
0 %
0 %
Cooling 2
>
SEQ-J
Off
Off
0 %
0 %
External
heating/cooling
capacity
>
Note:
Off = Sequence not activated. Sequence with lower number activates before sequence with higher number.
In software version 4.0–1–05 the term “Off” is replaced with “No”.
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Functions
3. Select
Function activation
4. Select
Heating/Cooling sequence setup
5. 5. Assign the activation order for the cooling sequence by selecting number (1-10) in column
Cooling
for
SEQ-C
,
-H
or
-J