15
Example 6: Alarm configuration
Configuration > Alarms
2021–03–01
Alarm delay at start up
60 s
Search alarm no:
53
Filter alarm supply air
>
Air and temperature control
>
Extra functions
>
Extra sensors and alarms
>
Fire/Smoke
>
Component malfunction
>
Manual operation and warnings
>
Configuration > ... > Filter alarm supply air
2021–03–01
Action:
No action
Level:
Class B
Delay:
300 s
Limit X1:
0 m
3
/h
Limit Y1:
10 Pa
No:
53
Limit X2:
2000 m
3
/h
Limit Y2:
150 Pa
Name:
Filter alarm supply air
Original name:
Filter alarm supply air
6.1.6
System information
Shows information about the air handling unit, installation site, control unit, communication and the
Systemair product. To enter information, such as site specific unit name or server partner’s contact
information, go to
System information setup
with user level
Service
.
Example 7: System information
System information
2021–03–01
Unit information
Installation address
Service partner
Communication
Access Control Unit
Systemair product
System information setup
>