58
14.4.11.3 Allocation
Select I/O (in-output) placement of where the heater control signal output, pump start output and pump feedback input
are connected to the controller in the
Configuration
>
I/O allocation settings
submenus
Digital inputs
,
Analog outputs
and
Digital outputs
.
Overview:
Configuration
>
I/O allocation settings
>
Digital
inputs
2021–03–01
Digital inputs
Device
Position
Feedback heating (SEQ-A)
Controller
UI4
Configuration
>
I/O allocation settings
>
Analog
outputs
2021–03–01
Analog outputs
Device
Position
Heating (SEQ-A)
Controller
AO4
Configuration
> ... >
Analog outputs
>
Heating (SEQ-A)
2021–03–01
Range output
0-10 V
Configuration
>
I/O allocation settings
>
Digital
outputs
2021–03–01
Digital outputs
Device
Position
Heating pump (SEQ-A)
Controller
DO1
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
I/O allocation settings
3. Select
Digital inputs
4. Select the input connected to the circulation pump’s feedback contact (e.g.
UI4
) as position for
Feedback heating
(SEQ-A)
5. Go back to
I/O allocation settings
(use the navigation path
Configuration
>
I/O allocation
settings
)
6. Select
Analog outputs
7. Select the analog output connected to the valve actuator control signal (e.g.
AO4
) as position for
Heating (SEQ-A)
8. Select
Heating (SEQ-A)
9. Adjust
Range output
to fit with the signal range of the valve actuator (e.g. 0-10 V)
10.Go back to
I/O allocation settings
(use the navigation path
Configuration
>
I/O allocation
settings
)
11.Select
Digital outputs
12.Select the digital output connected to the circulation pump (e.g.
DO1
) as postion for
Heating pump (SEQ-A)
.
254051 | A001