41
14.4.4.4 Operation settings
Data & Settings
>
Temp Control
>
Supply air
controller
2021–03–01
Min limit supply air
14.0 °C
Max limit supply air
30.0 °C
Step by step:
1.
Select
Data & Settings
from the navigation icons
2. Select
Temperature control
3. Select
Room controller
4. Adjust
Setpoint room
to the desired temperature setpoint
5. Go back to
Temperature control
(use the navigation path
Data & Settings
>
Temperature control
)
6. Select
Supply air controller
7. Set
Min limit supply air
to the lowest permitted supply air temperature
8. Set
Max limit supply air
to the highest permitted supply air temperature.
14.4.5
Extended operation
14.4.5.1 Activation
Select
Yes
on
Extended operation
in the
Configuration > Functions > Function activation
menu.
Overview:
Configuration
>
Functions
>
Function activation
2021–03–01
Extended operation
Yes
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Functions
3. Select
Function activation
4. Select
Yes
on
Extended operation
.
14.4.5.2 Configuration
Select which of the configured fan speeds to enable extended operation for in the
Configuration
>
Functions
>
Extended operation
menu.
Overview:
Configuration
>
Functions
>
Extended operation
2021–03–01
Extended operation low speed
No
Extended operation normal speed
Yes
Extended operation high speed
Yes
Step by step:
254051 | A001