61
Configuration
> ... >
Analog outputs
>
Changeover 1
2021–03–01
Range output
0-10 V
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
I/O allocation settings
3. Select
Digital inputs
4. Select the input connected to the heating/cooling feedback (e.g.
DI4
) as position for
Cooling/(Heating)
changeover 1
5. Go back to
I/O allocation settings
(use the navigation path
Configuration
>
I/O allocation
settings
)
6. Select
Analog outputs
7. Select the analog output connected to the control signal (e.g.
AO4
) as position for
Changeover 1
8. Select
Changeover 1
9. Adjust
Range output
to the desired voltage range (e.g.
0-10 V
).
14.4.13 External stop
14.4.13.1 Activation
Set
External stop
to
Yes
in the list of available functions in the
Configuration
>
Functions
>
Function ac-
tivation
menu.
Overview:
Configuration
>
Functions
>
Function activation
2021–03–01
External stop
Yes
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Functions
3. Select
Function activation
4. Select
Yes
as
External stop
.
254051 | A001