38
Caution
Do not use the same in- or output for several functions.
Overview:
Configuration
>
I/O allocation settings
>
Analog
inputs
2021–03–01
Analog inputs
Device
Position
Pressure supply air
Controller
UI2
Pressure extract air
Controller
UI1
Configuration
> ... >
Analog inputs
>
Pressure supply
air
2021–03–01
Min volt input (Vmin)
0.0 V
Max volt input (Vmax)
10.0 V
Sensor value at Vmin
0.0
Sensor value at Vmax
500.0
Step by step:
1.
Select
Configuration
from the navigation icons
2.
Select I/O allocation settings
3. Select
Analog inputs
4. Select the input connected to the sensor (e.g.
UI2
) as position for
Pressure supply air
5. Select the input connected to the sensor (e.g
UI1
) as position for
Pressure extract air
6. Select
Pressure supply air
7. Set
Sensor at Vmin
the same as the start point of the sensor’s selected measuring range
8. Set
Sensor at Vmax
the same as the end point of the sensor’s selected measuring range
9. Set
Min volt input (Vmin)
and
Max volt input (Vmax)
to values corresponding to the sensor’s signal type (e.
g. 0…10V, 2…10V etc.)
10.Go back to
Analog inputs
(use the navigation path
Configuration
>
I/O allocation settings
>
Analog
inputs
)
11.Select
Pressure extract air
and repeat steps 7 through 9.
254051 | A001