37
14.4.2
Alarm configuration
Configure any alarm available in the controller in the
Configuration
>
Alarms
menu.
Overview:
Configuration
> ... >
Extra alarm 1
2021–03–01
Action:
No action
Level:
Disabled
Delay:
0 s
No:
68
Name:
Extra alarm 1
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Alarms
3. Select the desired alarm after scrolling through the list of all alarms and identifying the alarm via either name or alarm
number
4. Select the action the unit will take when the alarm is active (e.g
Normal stop
) as Action
5. Select the desired Alarm class or disable the alarm (e.g
Class B
) as Level
6. Adjust the time before the alarm activates as
Delay
7. Adjust the name of the alarm as
Name.
14.4.3
Fan control type (Pressure)
14.4.3.1 Activation
Activate pressure control.
Select
Fan control type
as
Pressure
in the
Configuration
>
Functions
>
Function activation
menu.
Overview:
Configuration
>
Functions
>
Function activation
2021–03–01
Fan control type
Pressure
Step by step:
1.
Select
Configuration
from the navigation icons
2. Select
Functions
3. Select
Function activation
4. Select
Pressure
as
Fan control type
.
14.4.3.2 Allocation
Setup differential pressure sensors.
Select I/O (in-/output) placement for where the differential pressure sensors are connected. Set the sensors’ signal and
corresponding measuring range in the
Configuration
>
I/O allocation settings
>
Analog inputs
menu.
254051 | A001