![Symmetricom TimeSource 3600 Manual Download Page 86](http://html.mh-extra.com/html/symmetricom/timesource-3600/timesource-3600_manual_1419630086.webp)
86
TimeSource 3600
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
E1 or Analog Synchronization Outputs
Warning:
Because the E1 output circuits do not provide
lightning protection, do not connect the E1 output line
directly to a point outside the building. Failure to observe this
warning may result in equipment damage.
Connect the E1 or analog synchronization outputs at the wire-
wrap pins or BNC connectors labeled E1 OUT A and E1 OUT B. If
using the wire-wrap pins, connect the tip wire to the pins labeled
T, the ring wire to the pins labeled R, and the shield to the pins
labeled S. See Figure 24 for the location of the connectors and
pins, and Figure 26 for the wire-wrap connections.
Notes:
1. For wire-wrap connections, the shield pin is provided to ground
the cable shield at the shelf, if required. Normally, the shield is
grounded at the source. Grounding the shield at both ends is not
recommended.
2. A BNC connector can be used for one output, and a wire-wrap
connector can be used for the other output, but do not use the
BNC and wire-wrap connectors of the same output
simultaneously. For example, a BNC connector can be used for
output A and the wire-wrap pins for output B, but do not use
the output A BNC connector with the output A wire-wrap
connector.
Figure 26. E1 or Analog Output Wire-Wrap Connections
T
R
S
T
R
S
B
A
Summary of Contents for TimeSource 3600
Page 1: ...TimeSource 3600 GPS Primary Reference Source 097 72060 01 Issue 2 ...
Page 4: ...4 TimeSource 3600 This page intentionally left blank ...
Page 16: ...16 TimeSource 3600 This page intentionally left blank ...
Page 121: ...4 Chapter TL1 Reference This chapter provides information for using the TL1 language ...
Page 223: ...6 Chapter Specifications This chapter provides equipment specifications ...
Page 247: ...Index ...