![Symmetricom TimeSource 3600 Manual Download Page 213](http://html.mh-extra.com/html/symmetricom/timesource-3600/timesource-3600_manual_1419630213.webp)
5
Troubleshooting
213
2
3
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
COM-x USER
TIMEOUT LOGOFF
The user was auto logged off.
If COM-x is the port this message was
received on, retry logging in. If not, none
required.
DISCONNECTED
USER LOGOFF
A user was logged off by the
system administrator.
None required.
HOLDOVER
All inputs (GPS signal, span
inputs) are lost or
unacceptable. The system is
using the internal oscillator.
None required.
Becomes major alarm after 72 h.
CRITICAL ACO
EVENT
The ACO pushbutton has
been pressed to deactivate a
critical audible alarm.
None required.
DOWNLOAD
FAILED
The software download has
failed.
Retry the software download.
DOWNLOAD IN
PROGRESS
Software is being downloaded.
Wait until the download has been
completed.
DOWNLOAD
SUCCESSFUL
The software has been
downloaded successfully.
None required.
GPS ERROR
The GPS receiver is reporting
an error.
None required.
Becomes minor alarm after 10 h.
MAJOR ACO EVENT
The ACO pushbutton has
been pressed to deactivate a
major audible alarm.
None required.
MINOR ACO EVENT
The ACO pushbutton has
been pressed to deactivate a
minor audible alarm.
None required.
POWER UP RESTART
The system processor has just
started up.
None required.
Table L. Message Troubleshooting (cont’d)
Message
Meaning
Action
Summary of Contents for TimeSource 3600
Page 1: ...TimeSource 3600 GPS Primary Reference Source 097 72060 01 Issue 2 ...
Page 4: ...4 TimeSource 3600 This page intentionally left blank ...
Page 16: ...16 TimeSource 3600 This page intentionally left blank ...
Page 121: ...4 Chapter TL1 Reference This chapter provides information for using the TL1 language ...
Page 223: ...6 Chapter Specifications This chapter provides equipment specifications ...
Page 247: ...Index ...