4-22
Sun Server X2-4 Service Manual • April 2013
▼
Install a PCIe Card
Refer to
FIGURE 4-10
when completing the following procedure.
Caution –
This procedure requires that you handle components that are sensitive to
static discharge. This sensitivity can cause the component to fail. To avoid damage,
ensure that you follow antistatic practices as described in
Section 2.3 “Performing
Electrostatic Discharge and Static Prevention Measures” on page 2-3
.
Caution –
Ensure that all power is removed from the server before removing or
installing PCIe cards. You must disconnect the power cables before performing this
procedure.
1. Unpack the PCIe card and place it on an antistatic mat.
2. Ensure that the server is powered off and all power cords are disconnected from
the server power supplies.
See
Section 2.6 “Powering Off the Server” on page 2-6
.
3. Install the PCIe card into the PCIe card slot.
FIGURE 4-10
Installing a PCIe Card
4. Return the PCIe card slot crossbar to its closed and locked position.
5. Return the server to operation:
Summary of Contents for Fire X4470 M2
Page 1: ...Sun Server X2 4 formerly Sun Fire X4470 M2 Service Manual Part No E20784 06 April 2013...
Page 14: ...xiv Sun Server X2 4 Service Manual April 2013...
Page 38: ...2 12 Sun Server X2 4 Service Manual April 2013...
Page 54: ...3 16 Sun Server X2 4 Service Manual April 2013...
Page 84: ...4 30 Sun Server X2 4 Service Manual April 2013...
Page 106: ...5 22 Sun Server X2 4 Service Manual April 2013 FIGURE 5 11 Installing the Motherboard...
Page 153: ...Appendix A Server Specifications A 3...
Page 154: ...A 4 Sun Server X2 4 Service Manual April 2013...
Page 167: ...Appendix B BIOS Setup Utility Menus B 13 FIGURE B 16 BIOS PCIPnP Menu Second Screen...
Page 176: ...B 22 Sun Server X2 4 Service Manual April 2013...
Page 182: ...C 6 Sun Server X2 4 Service Manual April 2013...