Chapter 3
Using DC Power
15
Assembling the DC Input Power Cable
▼
To Assemble the DC Input Power Cable
1. Determine how many DC input power cables you will need from each DC power
source.
2.Turn off power to the DC power source through the circuit breakers.
Caution –
Do not proceed with these instructions until you have turned off the
power to the DC power source through the circuit breakers.
3. Take a DC connector from the ship kit.
4. Locate the three wires coming from the DC power source that will be used in the
connection to your unit:
■
–48 V Supply
■
Chassis ground
■
–48 V Return
5. Strip 8 mm (0.31 inches) of insulation from each of the wires coming from the DC
power source (see
Do not strip more than 8 mm (0.31 inches) from each wire. Doing so will leave
uninsulated wire exposed from the DC connector after the assembly is complete.
FIGURE 3-1
Stripping the Insulation From the Wire
6. Insert the tip of the cage clamp operating lever into the rectangular hole directly
above the hole in the DC connector where you want to insert the first wire and
press down on the cage clamp operating lever (see
This opens the cage clamp for this section of the DC connector.
8 mm (0.31 in.)
SysAdmin.book Page 15 Friday, March 30, 2001 2:38 PM
Summary of Contents for Netra t1 100
Page 21: ...PART I Installation and Configuration SysAdmin book Page 1 Friday March 30 2001 2 38 PM...
Page 22: ...SysAdmin book Page 2 Friday March 30 2001 2 38 PM...
Page 95: ...PART II Maintenance and Management SysAdmin book Page 73 Friday March 30 2001 2 38 PM...
Page 96: ...SysAdmin book Page 74 Friday March 30 2001 2 38 PM...
Page 121: ...PART III Appendices SysAdmin book Page 99 Friday March 30 2001 2 38 PM...
Page 122: ...SysAdmin book Page 100 Friday March 30 2001 2 38 PM...