12.7.6
CH
WITH ANALOGUE INPUT CONTROL OF POWER OUTPUT
;
CH
MODE
5
In this mode of operation, the boiler power (boiler input) is controlled by an analogue input signal provided by a
remote means such as a Building Management System or a system controller. The analogue input 0-10 VDC is
used to adjust the boiler power output between the minimum boiler input and the maximum boiler input settings.
The minimum analogue input signal value will correspond to the minimum modulation rate and the maximum
modulation analogue input signal value will correspond to the maximum modulation rate.
All other safety and control functions associated with the boiler will react normally to adverse condition and override
control of the analogue signal to prevent an upset condition.
A heat request will be generated by an input of 1.5 volts or higher. The fan speed modulation will occur between
2.0 and 9.0 volts. The request for heat will stop when the voltage drops below 1 volt.
CH mode 5 will work without sensors.
Parameters
Level
(Default) Value
Settable
CH_Mode
2: Installer 0
Mode 0, 1, 2, 3, 4, 5
Figure 12. 1