![Strebel S-CBX 105 Installation Operating & Maintenance Manual Download Page 116](http://html.mh-extra.com/html/strebel/s-cbx-105/s-cbx-105_installation-operating-and-maintenance-manual_1384114116.webp)
116
Burner door thermostat
Needed Tool: Wrench 16 mm.
This thermostat is activated if the temperature of the burner door has
been too high. In this case, it has to be replaced (spare part).
Replacement:
- Disconnect the wiring and remove the thermostat.
- Tighten the burner door’s thermostat with a torque of 2 Nm.
- Reconnect the wiring.
Burner door gaskets
If any part of a gasket has discoloured, changed texture, or hardened then, the rubber has cured and/or has
damages, these gaskets must be replaced. Notice: Only use the gaskets that are supplied by the boiler
manufacturer.
Burner door gasket replacement:
- Remove the old gasket
- Place a new gasket in its groove.
- Respect the mounting direction.
Picture 19.4
Picture 19.5