98
15.2.7 P
OWER MODE
=
1
(M
INIMUM BOILERS ON
)
Power Mode 1 guarantees to have as minimum as possible dependent ON in order to reach the T_System.
The modulation of most boilers/burners is forced to 100%, and the last 2 boilers/burners are PID controlled by the
setpoint (Cascade_Setpoint) from the managing burner in relation to the system temperature (T_System).
The last 2 boilers/burners are modulating to make sure that the power can be adapted to the system temperature
without continuous cycling of the last burner(s).
Below a picture that shows an example with 5 boilers/burners.
Burner Start-up
The next burner is started under the following conditions:
• At least one PID controlled depending is operating at a power [%] > Start_Power_Threshold [%].
The managing burner forces another burner to 100% power and waits for 3 min. (Start_Next_Depending_Delay,
settable) before another burner can be started.
Burner shut down
The last started burner will be stopped under the following conditions:
• All PID controlled depending in burn state Power [%] < Stop_Power_Threshold [%] The managing burner
releases another burner for PID control and waits for 3 min. (Stop_Next_Depending_Delay, settable) before
another burner can be stopped.
Relevant variables
Specific Parameters
Level
(Default) Value
Range
Power Mode
2: Installer
3
0…3
Start_Power_Threshold
Threshold rate before starting the next burner. Condition: at
least 1 depending in burn state power [%] >
Start_Power_Threshold[%]
2: Installer
80%
1…100%
Stop_Power_Threshold
Threshold rate before starting the next burner. Condition:
all depending in burn state Power [%] <
Stop_Power_Threshold [%]
2: Installer
25%.
1…100% .
Start_Next_Depending_Delay
When the timeout is over the last dependent can be started
2: Installer
200 sec.
0…1275 sec.
Stop_Next_Depending_Delay
When the timeout is over the last dependent can be
stopped
2: Installer
180 sec.
0…1275 sec.
Hyst_Up_Stop_Burner
Hysteresis to stop burner. Condition: T_System above
Cascade_Se Hyst_Up_Stop_Burner
2: Installer
5 sec.
9 sec.
0…20 sec.
0…36 sec.
Hyst_Down_Start_Burner
Hysteresis to start burner. Condition: T_System below
Cascade_Setpoint - Hyst_Down_Start_Burner
2: Installer
5 sec.
9 sec.
0…20 sec.
0…36 sec.