![Strebel S-CBX 105 Installation Operating & Maintenance Manual Download Page 47](http://html.mh-extra.com/html/strebel/s-cbx-105/s-cbx-105_installation-operating-and-maintenance-manual_1384114047.webp)
47
Examples A (C63) and B (C33) maximum pipe lengths
Example B (C33)
Boiler Type
→
S-CBX 85 S-CBX
105
S-CBX
125
S-CBX
155
Diameter air pipe
[mm]
100
100
100
NOT
POSSIBL
E
Diameter flue pipe
[mm]
100
100
100
Concentric roof terminal [mm]
100/150
100/150
100/150
Maximum pipe length [m]
(flue & air total pipe length)
includes: 4 bends 90°
adaptor par-conc
conc. roof terminal
8.3
-
-
Example A (C63)
Boiler Type
→
S-CBX 85 S-CBX
105
S-CBX
125
S-CBX
155
Diameter air pipe
[mm]
100
100
100
150
Diameter flue pipe
[mm]
100
100
100
150
Diam. roof terminals
[mm]
100
100
100
150
Maximum pipe length [m]
(flue & air total pipe length)
includes: 4 bends 90°
flue outlet zeta = 1.0
air inlet zeta =1.0
40.8
21.2
5.9
108.1
Concentric roof terminal
Air inlet
Flue outlet
Example A
C63
Example B
C33
concentric/
parallel adaptor
Summary of Contents for S-CBX 105