3.3 ErP Specifications Datasheet
Technical parameters according to the European ERP (Energy Related Products) legislation:
Type Boiler:
S-CBX 85 S-CBX 105 S-CBX 125 S-CBX 155
Condensing boiler:
Yes
Yes
Yes
Yes
Low temperature boiler:
No
No
No
No
B11 boiler:
No
No
No
No
Cogeneration space heater:
No
No
No
No
Combination heater:
No
No
No
No
Unit:
Value
Value
Value
Value
Rated heat output
kW
78.9
94.3
115.6
140.9
P-rated (P4) at 60-80
⁰
C
kW
78.9
94.3
115.6
140.9
Heat output (P1) 30% at 30-37
⁰
C
kW
25.2
31.6
38.8
46.5
Seasonal space heating energy
efficiency (ɳs).
%
92.4
92.6
92.7
92.9
Energy efficiency (ɳ4) at 60-80
⁰
C
%
87.2
87.2
87.3
87.3
Energy efficiency (ɳ1) at 30-37
⁰
C
%
97.4
97.6
97.7
97.8
Auxiliary electricity consumption
At full load (elmax).
kW
0.183
0.271
0.280
0.278
At part load (elmin)
kW
0.024
0.023
0.027
0.031
In standby mode (Psb)
kW
0.007
0.007
0.007
0.007
Other
Standby heat loss (Pstby)
kW
0.066
0.070
0.075
0.083
Ignition burner power consumption (P
ign
)
kW
0.000
0.000
0.000
0.000
Emissions (NOx) of nitrogen oxides
(EN15502-1:2012+A1:2015)
1
mg/kWh
23.1
21.3
23.9
20.1
Sound power level, indoors
(EN 15036-1:2006)
dB
65.8
68.0
67.8
73.0
1
These numbers are used to assign credits according to the BREEAM standards
Summary of Contents for S-CBX 105
Page 2: ......
Page 40: ...40 9 10 Flue Terminal Positioning ...
Page 42: ...42 9 11 1 FIGURE 12 LINE G ...
Page 55: ...55 11 5 Ladder Logic Diagram ...
Page 56: ...56 11 6 Electrical schematics ...
Page 57: ...57 ...
Page 137: ......