59
11.9 Programmable in- and outputs
It’s possible to re-program some in- and outputs to other functions. To do this use below list and go to:
Menu\settings\boiler settings\"1122" (installer password) \boiler parameters
boiler parameter name
default setting description
terminal
(117)
Prog. Input 2.
2
DHW flow switch
LV 16-17
(118)
Prog. Input 3.
2
Gas pressure switch LV 24-25
(122)
Prog. Input 7.
3
Cascade sensor
LV 3-4
(124)
Prog. Input RT. 1
room thermostat on
LV 12-13
(125)
Prog. Output 1. 4
System pump
HV 4-5
(126)
Prog. Output 2. 9
Ext. Igniter
separate connector
(127)
Prog. Output 3. 6
Alarm relay
HV 10-11
(128)
Prog. Output 4. 18
3-way Valve DHW
HV 3-2-1
To all outputs following applies: maximum current 1.5 A each output.
Total output of all currents combined maximum 3.5 A.
The inrush current of the 3-way valve and/or pumps is maximum 8 A.
boiler
para-
meter
Display:
INPUTS:
boiler
para-
meter
Display:
OUTPUTS
:
(117) Prog. Input 2.
0 Disabled
(127)
Prog. Output 3.
0 Disabled
1 DHW flow sensor
1 Module pump
2 DHW flow switch
2 CH pump
3 CH flow sensor
3 DHW pump
4 CH flow switch
4 System pump
(118) Prog. Input 3.
0 Disabled
5 Cascade pump
1 Drain switch ?
6 Alarm relay
2 Gas pressure switch
7 Filing valve
(122) Prog. Input 7.
0 Disabled
8 LPG tank
1 T_Flue_2 sensor
9 Ext. Igniter
2 T_Flue_2 with blocked flue?
10 Air damper
3 Cascade sensor
(128)
Prog. Output 4.
0 Disabled
4 Blocked Flue switch
1 Module pump
5 CH Sensor
2 CH pump
(124) Prog. Input RT.
0 room thermstat off
3 DHW pump
1 room thermstat on
4 System pump
Display:
OUTPUTS
:
5 Cascade pump
(125) Prog. Output 1.
0 Disabled
6 Alarm relay
1 Module pump
7 Filing valve
2 CH pump
8 LPG tank
3 DHW pump
9 Ext. Igniter
4 System pump
10 Air damper
5 Cascade pump
11 empty
6 Alarm relay
12 empty
7 Filing valve
13 empty
8 LPG tank
14 empty
9 Ext. Igniter
15 empty
10 Air damper
16 empty
(126) Prog. Output 2.
0 Disabled
17 3-way Valve CH
1 Module pump
18 3-way Valve DHW
2 CH pump
19 3-way Valve CH
(power when idle)
3 DHW pump
20 3-way Valve DHW
(power when idle)
4 System pump
5 Cascade pump
6 Alarm relay
7 Filing valve
8 LPG tank
9 Ext. Igniter
10 Air damper
NOTICE
Summary of Contents for S-CBX 105
Page 2: ......
Page 40: ...40 9 10 Flue Terminal Positioning ...
Page 42: ...42 9 11 1 FIGURE 12 LINE G ...
Page 55: ...55 11 5 Ladder Logic Diagram ...
Page 56: ...56 11 6 Electrical schematics ...
Page 57: ...57 ...
Page 137: ......