P32-EN – Subject to technical changes 04.11
61
Technician
Appendix: Information on SolvisControl system controller
The following lists the designations, switch states, pump
speeds and mixer states as displayed at the outputs. You
can set the switch states (“HAND/ON” – “HAND/OFF” –
“AUTO/...” -), where the respective state is indicated by
“AUTO/OFF” or “AUTO/ON” based on the current condition.
The outputs are assigned as follows:
1: Swimming pool pump contactor (“Pool pump”)
To control both pumps for heating the swimming pool,
parallel to the primary swimming pool pump, you have
to connect a contactor at output 1.
2: Hot water pump (“WW Pump”)
The speed of the hot water pump is controlled in the
“AUTO/...” setting (
section 9.4
). The speed level is
displayed.
3: Heating circuit pump 1 (“Heat C Pump1”)
The pump for the first mixed heating circuit can be
switched on or off in the “AUTO/...” setting depending
on your needs (
section 9.2
).
4: Heating circuit pump 2 (“Heat C Pump2”)
The pump for the second mixed heating circuit can be
switched on or off in the “AUTO/...” setting depending
on your needs (
section 9.3
).
5: Circulation pump (“Circu Pump”)
The circulation pump can be switched on or off in
the “AUTO/...” setting depending on your needs
(
section 9.7
).
6:
“
Solar Pump1”
The speed of the solar pump in the primary circuit is
controlled in the “AUTO/...” setting (
section 10.3.2
),
and that speed is displayed here.
7:
“
Solar Pump2”
The speed of the solar pump in the secondary circuit is
controlled in the “AUTO/...” setting (
section 10.2.1
),
and that speed is displayed here.
11.1.2 “Outputs” menu item
8: Heating circuit mixer 1 open (“Mix Heat Cyc1”)
The mixer in heating circuit 1 can automatically open
wider if you need it to. Behind the switch state “off: OFF”
you can open the mixer in manual mode (
page 28, top
).
9: Heating circuit mixer 1 closed (“cl: OFF”)
The mixer in heating circuit 1 can automatically close
more if you need it to. Behind the switch state “cl.: OFF”
you can close the mixer in manual mode (
page 28, top
).
10: Heating circuit mixer 2 open (“Misch.Hzkr2”)
The mixer in heating circuit 2. For an explanation,
refer to output 8.
11: Heating circuit mixer 2 closed (“cl: OFF”)
The mixer in heating circuit 2. For an explanation,
refer to output 9.
12: Requirement boiler (“Req.Burner”)
The automatic firing system of the boiler receives a
signal to start the boiler when there is a need for
heat and the unit is set to “AUTO/...” (
section 9.9
).
13: Charging pump
(“
Load pump”)
Pump for charging the SolvisStrato buffer tank by
external boiler. The after run was set to 2 min in the
factory and can be set (in “Technician” mode) under
“Outputs” – “13: LOAD PUMP” – “AFTER RUN:”.
14: “Data line”
For connection of a data logger or bootloader.
15: “Analog output”
Modulation signal 0 to 10 V for gas or oil boiler.