P32-EN – Subject to technical changes 04.11
31
Technician
Setting the controller and start-up
8.8 Connecting the swimming pool sensor (optional)
A swimming pool should be heated as shown in the dia-
grams on
pages 67f
. Install sensor S16 as an immersion
sensor in the swimming pool discharge to the filter.
After connecting the sensor and pump, you must:
1. Change the sensor type for input S16,
2. Deactivate the room sensor in function “17:HEAT CIR.1”
and
3. Set the heating times to conventional swimming pool
heating. Settings only as of “Technician” operating mode
(
page 25
).
1. Settings for sensor type input S16
Step 1
: In the function overview, turn the rotary wheel to
the entry “INPUTS” and press it. In the Inputs menu, go
to “PAR?” beneath the entry “16: Temp.Room1” and
press the rotary wheel.
Step 2
: Turn the rotary wheel in the menu that opens up
until the pointer is on “DES: Temp.Room1”. Press and
turn the rotary wheel until you see “T.swimming pool”
and press the rotary wheel to save the entry.
Step 3
: Go to the entry “SENSOR: RAS”. Press and turn
the rotary wheel until you see “KTY 10” and press it to
save the entry.
The
figure on the right
summarizes the settings.
Step 1
: In the function overview, turn the rotary wheel
until the pointer is behind “HEAT CIR.1 F:17” and press
it once.
Step 2
: Now go to entry “INPUT VARIABLE:” and press
the rotary wheel once.
Step 3
: Now turn the rotary wheel until the pointer is
behind “Source: Input” below the entry “ROOM TEM-
PERATURE” and press it.
Step 4
: Now turn the rotary wheel until the entry “Oper-
ator” appears and press it again to save this value.
The
figure on the right
summarizes the settings.
Settings for the swimming pool
sensor
Sensor menu:
1 2 3 4 5 6 7 8 9 10 11 12 13 14
INPUT 16
TYPE: ANALOG
MEASURED VALUE:
Temperature
DESIGNATION
GROUP: General
DES: T. swimming pool
SENSOR: KTY
10
SENSOR CHECK: Yes
SENSOR CORR.: 0.0 K
MEAN VALUE: 1.0 sec
BROWSE
BACK
2. Deactivating the room sensor in function 17
3. Setting the heating times
When the sun shines, the unused solar heat is to be used
for heating the swimming pool to the target temperature. If
you want to use the swimming pool at particular times, you
must set these as auxiliary heating times . . . . . .
page 45
1 2 3 4 5 6 7 8 9 10 11 12 13 14
BACK
ROOM TEMPERATURE:
Source:
User
unused
INPUT VARIABLE
Room sensor in function “17:HEAT CIR.1”
deactivated
If the controller is used for swimming pool heating,
you can no longer connect a room sensor because
it also uses input S16.