P32-EN – Subject to technical changes 04.11
27
Technician
Follow the instructions in the three sections of start-up. All
hydraulic circuits in the system must be professionally prior
to start-up.
Setting the controller and start-up
8.5 Start-up and sensor installation
•
Set time and date . . . . . . . . . . . . . . . . . . . . .
page 12
•
If a room sensor (accessories,
page 14
) has been con-
nected, activate it in function 17 as follows:
Only heating circuit 1 can be equipped with a
room sensor. It is not possible to heat a swim-
ming pool in addition to this. Connect the room
sensor at input S16, contrary to the installation
instructions (
page 66
).
• With connected room sensor only
: If the room tempera-
ture is to be used to determine the flow temperature,
set the room influence factor . . . . . . . . . . . . .
page 15
•
Hiding malfunction messages from sensors that are
not connected (disabling sensor check).
If there are not collectors, for example, sensor check
sensor 8 should be deactivated . . . . . . . . . . .
page 22
•
Perform a plausibility check of the inputs (e. g. check the
temperature on the heating circuit flow against controller
values). Call the “Inputs” submenu in the main menu.
Sensor value “9999” means that no sensor is connected
or there is sensor/cable breakage. “-999” indicates a
short circuit.
•
Perform a function check of the outputs (pumps). When
the volume flow sensor is attached, operate the relevant
pump in “HAND/ON” mode and check the volume flow
display on the SolvisControl. Set the quantity per impulse
(impulse rate), if necessary. . . . . . . . . . . . . . .
page 30
Make a backup copy at the SolvisControl after com-
pleting any adjustments to the settings.
8.5.1 General settings and plausibility check
All temperature sensors in the secondary circuit,
except for the solar flow and return sensors
(= Pt 1000), are of resistance type PTC 2 kOhm.
You can find a measurement value table for
checking the sensors in the
appendix on page 65
.
Step 1
: In the function overview, turn the rotary wheel
until the pointer is behind “HEAT CIR.1 F:17” and press
it once.
Step 2
: Now go to entry “INPUT VARIABLE:” and press
the rotary wheel once.
Step 3
: Now turn the rotary wheel until the pointer is
behind “Source: User” below the entry “ROOM TEMPER-
ATURE” and press it.
Step 4
: Now turn the rotary wheel until the entry “Input”
appears and press it again to save this value. In the
line below, as just descrbed, set “16: Temp.Room1”.
An overview of the settings is shown on the right.
1 2 3 4 5 6 7 8 9 10 11 12 13 14
BACK
ROOM TEMPERATURE:
Source:
Input
16 : T.Room1
INPUT VARIABLE
Room sensor in function “17:HEAT CIR.1” activated