Technician
Setting the controller and start-up
8.1 Safety notes
In case of danger
:
•
Turn off mains voltage immediately.
•
In case of fire use suitable fire extinguisher.
•
Close oil or gas valve.
Observe regulations
:
Read the following information about start-up thoroughly
before you commission the system. This prevents damage
to the system that can arise from improper handling.
Operate according to the recognised technical regulations.
Observe the accident prevention regulations of the Acci-
dent Prevention and Insurance Association. Incorrect use
and impermissible changes during installation and design
result in the exclusion of liability claims.
Wiring
:
The electrical connection takes place according to
the
section “Wiring plan SolvisControl control board”, p. 66.
The setting options for the SolvisControl are available in
three different operating modes. They provide protection
against accidental changes. System operators should
always select the “Client” operating mode.
All the following settings are made in the “Client”
operating mode unless stated otherwise.
Select the “User” menu item in the main menu by turning
and pressing the rotary wheel.
Now select the “Client” or “Technician”
*
operating mode
by turning and pressing the rotary wheel (figure on right).
Press the “BACK” button to return to the main menu.
1 2 3 4 5 6 7 8 9 10 11 12 13 14
USER
BROWSE
BACK
OPERATING MODE:
Client
Technician
Expert
Selecting operating mode (“User” selected). Change
to “Technician”
*
.
8.2 SolvisControl: Selecting the operating mode
* Enter the code for “Technician” mode by pressing,
turning and pressing the rotary wheel again.
8 Setting the Controller and Start-up
8.3 Transfer of the boiler temperature to modulating third-party boilers
You can transfer the required boiler temperature to a modu-
lating third-party boiler as an analogue voltage signal with
functions 36 and 37 using output 15.
In the “Outputs” menu, output 15 must be set with the
appropriate scaling.
Standard setting of scaling
:
150 scale divisions (= 15°C) are supplied with
0.6 V and900 scale divisions (= 90°C) are supplied
with 10.0 V.
You can only change the scaling in the “Expert” operating
mode.