Warning #
LCD text
Comments and troubleshooting
1-4, 6-7
Fan X Failure
Clean or replace the fan
5
Turn Switch Off to Configure
Appears when trying to access the Setup
menus during production
8
Connection Unit Low 9V Battery
Replace the 9V battery in the StorEdge
Connection Unit. Refer to
9V Battery
Replacement
on page 91.
StorEdge Connection Unit LEDs
There are three LEDs on the lower board of the StorEdge Connection Unit, near the DIP switches:
l
l
l
Figure 41: StorEdge Connection Unit LEDs
In normal operation, t
he middle and bottom LEDs indicate
auxiliary voltages (13V from DC/DC, 5V
and 3.3V)
and should always be lit.
The top LED should be lit when the inverter DC
voltage
is at least 200 Vdc
(check
w
hen both inverter
ON/OFF switch and StorEdge Connection Unit switch are ON). Y
ou can check the status screen for
the Vdc
value
.
If all LEDs are OFF:
o
Check that AC voltage exists in the inverter
o
Check that the communication cable between the StorEdge Connection Unit and the digital
board is properly connected.
l
If the top LED is ON, and middle and bottom LEDs are off - an internal failure has occurred. Contact
SolarEdge support.
Power Optimizer Troubleshooting
If the inverter status screen indicates that not all power optimizers are paired or not all are reporting (P_
OK xxx/yyy, and x<y), those optimizers can be identified through the LCD. Refer to
http://www.solaredge.com/files/pdfs/products/inverters/non-responding-power-optimizers.pdf