![SolarEdge storedge Installation Manual Download Page 31](http://html.mh-extra.com/html/solaredge/storedge/storedge_installation-manual_1313747031.webp)
Connecting to the Battery
To simplify the connection process it is advised to connect the battery to the inverter
before
mounting
the battery according to the manufacturer instructions.
Follow these guidelines:
l
For easy access to battery connectors, it is recommended to connect the cables to the battery and
to set all the battery DIP switches to their correct positions while the battery is still on the ground.
The following procedure is recommended:
a. Connect all the wires to the battery connection panel
b. Mount the battery
c. Assemble the conduit between the battery and the inverter
d. Connect to the StorEdge Connection Unit
l
Measure the necessary length between the StorEdge Connection Unit and the battery for all cables.
The maximum distance between the battery and the inverter is 35 ft/ 10m, when using 16AWG for
battery thermal power and 24AWG for battery control.
l
Tie and wrap the cables to avoid pulling them out during mounting.
l
Be sure to adhere to all safety cautions and information in the battery documentation.
l
The battery connects to the DC side of the inverter. Since the inverter DC connections are on its left
side, it is recommended to position the battery to the left of the inverter to simplify wiring.
NOTE
Per NEC requirements, if the battery is more than 5ft/ 1.5m away from the inverter, an additional
external DC switch ia required adjacent to the battery.
Prepare cables and connect as described in the following table (see
Figure 19
):
Recommended cable type
(min-max AWG)
StorEdge
Connection
Unit
connection
Tesla battery
connection
Connection method
DC
DC cable 10AWG (10-24 AWG),
600V insulated.
BAT DC +
terminal block
DC+
o
Insert a flat blade screwdriver into
the square opening at the top of the
terminal block and press to open
clamp mechanism.
o
Insert the wire into the round
opening and release the
screwdriver to spring back and
clamp the wire.
BAT DC-
terminal block
DC-
12V thermal power input
2-wire shielded twisted pair cable
16AWG (12-28AWG), 600V
insulated
Battery
Thermal V-
(black)
THERMAL -
Push the lever to open the connection,
insert the wire and release the lever
when the wire is clamped.
Battery
Thermal V+
(red)
T
SolarEdge
-
StorEdge Installation Guide MAN-01-00262-1.0
30