Cover installation BioX – wood log boiler 15 – 45
24
© Solarbayer GmbH [210205]
Yes
Yes
Yes
Yes
No
No
No
No
27.
Adjust the door contact switch
explanation:
To use the system safely, you have to adjust the door contact switch with the pressure senders (look at the
picture on the top). When one of the doors are open, the switch open the electric circuit too. If one of the
doors are open, the control board regulate the exhaust blower to full load, to generate an optimal smoke
outlet.
adjust the door contact switch :
Adjust as long the pressure senders that appears the “failure 13!” on the display, when min. one of the
doors are open. Therefore, you slack the lock nut and turn the pressure senders more out/in the door with
an Allan key.
open the filling
shaft- and heating
door
230 V
power on
failure 13! At
the display?
check the
mechanical switch
if you can move it +
check the
connection on the
control board
close
ONLY
the
filling shaft door.
failure 13! At the
display?
close
ONLY
the
heating door.
failure 13! At the
display?
close both doors.
failure 13! At the
display?
end
turn the pressure
sender of the filling
shaft door more
inside
turn the pressure
sender of the
heating door more
inside
turn all pressure
senders out of the
doors and check them
door contact
switch
pressure
sender