- 64 -
Option 1
(Occupied number
of stations of
CC-Link)
1,2,4
Set the operation mode for the controller (number of occupied
stations).
Parameter
Operation mode
(number of occupied stations)
1
Single numerical data instruction mode
(1 stations is occupied)
2
Half numerical data instruction mode
(2 stations are occupied)
4
Full numerical data instruction mode
(4 stations are occupied)
X
Undefined
parameter No.11
(Operation setting at
CC-Link
communication
error)
0,10
Set the operating method of CC-Link communication abnormality
(time-out, malfunction, and CRC error).
Parameter
Output the
data to
control unit
Details
0
Hold
(Hold the
operating
state)
Even if communication abnormality
occurs in CC-Link, the alarm does
not occur. The control unit continues
operation and executes it.
10
Alarm stop
When the communication
abnormality occurs in CC-Link, the
control unit will be stop state by the
alarm and outputs “Communication
alarm 150”.
X
Undefined
parameter No.12
Fixed
value
This is the fixed value for this controller.
(It should not be changed)
-
*1) The range varies depending on the electric actuator. Please refer to the manual of the electric actuator
for more details.
*2) It is recommended to set the “maximum speed” for the
electric actuator operation. Control is restricted
so that the set value is not exceeded. The response will be slower because of this.
*3) For the basic parameter "Parameter protection" to "3: Step", set it according to
the following procedures.
1. Start controller-setting software (LEC-W2) in the Normal mode.
2. Select "HELP" - "Password" from the menu and input "password" in the password input screen.
3. Change the basic parameter "Parameter protection" to "3: Step" in the
Parameter window.
4. Click "Download" to transmit the change. The text colour of the changed parameter will change
from blue to black.
5. After completing the setting, turn the LECPMJ OFF then ON to make the change effective.