- 23 -
4. Initial Setting
4.1 Switch (STATION NO., B RATE)
Set the CC-Link address and the CC-Link communication speed by the rotary switch. The table below
shows functions of switches.
●STATION NO
Switch name
Set range
Description
STATION NO.(X10)
01 to 64
Set upper bits of the station.
STATION NO.(X1)
Set lower bits of the station.
The CC-Link address setting at the time of the
factory shipment is set in “01".
●B RATE switch
B RATE
CC-Link
communication speed
9
Reset of Occupied number of stations
*1)
8
:
5
No used
4
10Mbps
3
5Mbps
2
2.5Mbps
1
625kbps
0
156kbps
The communication speed of CC-
Link setting at the time of the factory shipment is set in “0" (156kbps).
Example) When 3 controllers tie as follows by 2 stations occupation (The communication speed of
CC-Link is 10Mbps)
No. 1
No. 2
No. 3
PLC
LEC
PMJ
(3)
LEC
PMJ
(1)
LEC
PMJ
(2)
*1) In case of set point = 1 of Occupied
number of stations:
The set point of Occupied number of
stations is returns to “2” as delivered
by applying the power at the state of
B RATE = 9.
CC-Link
communication speed
10Mbps
LECPMJ (1) to (3)
Set the number of occupied
stations to 2
The station No. of CC-Link is shown. (01 to 64)
The communication speed of CC-Link is shown.