- 24 -
(1) Since the CC-Link communication speed of the PLC is 10 Mbps, set the B RATE switch for all
controllers to 4 (10 Mbps).
(2)
Set the controller’s STATION NO. (for the PLC, set the CC-Link station No. address to 0.)
Controller 1
:
For LECPMJ (1), set the CC-Link station No. address = 1.
(STATION NO. (X10)
=
0
、
STATION NO. (X1
=
1)
Controller 2
:
For LECPMJ (2), set the CC-Link station No. address = 3, which is calculated by adding
2 to the CC-Link station No. address of LECPMJ (1) (= 1).
(STATION NO. (X10)
=
0
、
STATION NO. (X1)
=
3)
Controller 3
:
For LECPMJ (3), set the CC-Link station No. address = 5, which is calculated by adding
2 to the CC-Link station No. address (= 3) of LECPMJ(2).
(STATION NO. (X10)
=
0
、
STATION NO. (X1)
=
5)
4.2 Parameter Setting
Set the parameter of occupied number of stations and operation setting at the time of the communication
error of LECPMJ. The set item is shown below.
●Occupied number of stations setting
Set Occupied number of stations in "Optional setting 1" of basic parameter item.
Optional setting 1
Mode
Occupied number of stations
1
Single numerical data instructions
1 stations
2 (initial value)
Half numerical data instructions
2 stations
4
Full numerical data instructions
4 stations
Please refer to
“9. Mode”
for details of each mode
●Operation setting of CC-Link at the time of the communication error
Set the operation of CC-Link at the time of the communication error
in “Undefined parameter No.11" of
basic parameter item.
Undefined parameter No.11
Output the data to control unit
0 (initial value)
HOLD
10
Alarm Stop
Please refer to
“11.2 Basic parameter”
for details of each parameter.