ACC7200 Air Compressor Controller User Manual Page 63 of 77
Table 15 Common Pressure Unit Conversion Table
Item
N/m
2
(pa)
kgf/cm
2
bar
(p/in
2
.psi)
1Pa
1
1.02x10
-
5
1x10
-
5
1.45x10
-
4
1kgf/cm
2
9.8x10
4
1
0.98
14.2
1bar
1x10
5
1.02
1
14.5
1psi
6.89x10
3
7.03x10
-
2
6.89x10
-
2
1
11
COMMISSIONING
It is suggested to do the following examination before formal system operation:
—
Check all the connections are correct and wire diameter is suitable;
—
Ensure that controller DC power has fuse, controller‘s positive and negative are correctly connected
to starting battery;
—
The emergency stop input is connected to the positive side of starting battery through the normal
closing point of the emergency stop button and fuse;
—
Take proper action to prevent engine from crank disconnect (e. g. Remove the connection wire of
fuel valve). If everything is OK, make the starting battery power on and controller will execute
routine.
—
Press “start” button, engine will start. After pre-set start times, controller will send failed to start
signal; then press “stop” to reset controller.
—
Recover the action of stop engine start (e. g. Connect wire of fuel valve), and press start button
again, then engine will start. If everything goes well, engine will go to normal running after idle
speed (if idle running is set). During this time, please observe engine’s running situation.
—
If there is any other question, please contact SmartGen’s service.