ACC7200 Air Compressor Controller User Manual Page 31 of 77
No.
Item
Range
Default
Description
Warning
Return
(0-100)%
30
Delay
(0-3600)s
5
19
CAN Data Upload
(0-1)
(0-1)
0
0: Disable; 1: Enable
( General Unit Invalid)
Air Compressor Setting
1
Air Com. Onload Speed
(0-100)%
64.0
Set value is the percentage
of rated speed; press
onload key and when
speed is up to load, load
control outputs.
2
Air Com. Unload Speed
(0-100)%
64.0
Set value is the percentage
of rated speed; when
discharge
pressure
reaches rated pressure
after load, make speed
steady at the set value.
3
Air Com. Target Pressure
(0-30000)kPa
700
Adjust
speed
at
corresponding upper limit
pressure value after load.
4
Air Com. Unload Act Press
(0-30000)kPa
600
Adjust
speed
at
corresponding lower limit
pressure value after load.
5
Raise Speed Rate Set
(30-500)r/s
150
Increased number of turns
per second.
6
Drop Speed Rate Set
(30-500)r/s
30
Reduced number of turns
per second.
7
Auto Load Control Set
(0-1)
0
0: Disable 1: Enable
(only ordinary units are
available)
8
Auto Drain Control
Set
Enable
(0-1)
0
0: Disable 1: Enable.
After enabled and air
compressor takes load,
“Auto
Drain
Control”
outputs as pre-set output
time and interval time.
Output Time
(0-3600)s
20
Interval Time
(0-36000)s
150
9
Overload Protect
Set
Set
(0-200)%
90
Set value is engine load
rate; return and delay
values can also be set.
Return
(0-200)%
70
Delay
(0-3600)s
5
10
Overload Drop Speed
(3-500)r/s
30
Decreased rotation number
per second.
11
Overload Maint. Speed
(0-100.0)%
70.0
Rated speed percentage;
After
protection
for
overload, compressor will
slow down; when it goes to
maint.
speed,
it
will