ACC7200 Air Compressor Controller User Manual Page 70 of 77
14.7
CUMMINS QSZ13
Engine type: Common J1939.
Table 27 Engine OEM Connector
Terminals of controller
OEM connector of engine
Remark
Auxiliary Output 1
45
AUX. Output 1 is configured as “29: Fuel
Relay Output” (The configuration is factory
default).
Auxiliary Output 2
-
AUX. Output 2 is configured as “28:
Starting Relay Output” (The configuration
is factory default).
Connect to starter coil directly.
Auxiliary
Output 3
16&41
AUX. Output 2 is configured as “30: Idle
Speed Control, normally close output”.
Make 16 connected with 41 during
high-speed running via external extended
relay.
-
-
CAN communication shielding wire.
CAN(H)
1
Using impedance 120Ω connecting line.
CAN(L)
21
Using impedance 120Ω connecting line.
14.8
DETROIT DIESEL DDEC III / IV
Engine type: Common J1939.
Table 28 Engine CAN Connector
Terminals of controller
CAN port of engine
Remark
Auxiliary Output 1
Extended
30A
relay,
providing battery voltage for
ECU.
AUX. Output 1 is configured as “29: Fuel
Relay Output” (The configuration is factory
default).
Auxiliary Output 2
-
AUX. Output 2 is configured as “28:
Starting Relay Output” (The configuration
is factory default).
Connect to starter coil directly.
-
-
CAN communication shielding wire.
CAN(H)
CAN(H)
Using impedance 120Ω connecting line.
CAN(L)
CAN(L)
Using impedance 120Ω connecting line.