ACC7200 Air Compressor Controller User Manual Page 53 of 77
8.2.3
DEFINED COMBINATION OUTPUT
Defined combination output is composed by 3 parts: OR conditional output S1, OR conditional output S2,
AND conditional output S3.
S1 or S2 is true, and S3 is true, then combination output outputs;
S1 and S2 both are false, or S3 is false, then combination output doesn't output.
NOTE:
S1, S2 and S3 can be any contents except itself defined combination output of the output settings.
NOTE:
S1, S2 and S3 cannot include or recursively include itself.
Contents of OR condition output S1: output port 1 is active;
Close when OR condition output S1 is active/inactive: close when active (disconnect when inactive);
Contents of OR condition output S2, output port 2 is active;
Close when OR condition output S2 is active/inactive: close when active (disconnect when inactive);
Contents of AND condition output S3: output port 3 is active;
Close when AND condition output S3 is active/inactive: close when active (disconnect when inactive);
When input port 1 is active or input port 2 is active, if input port 3 is active, defined combination output is outputting;
If input port 3 is inactive, defined combination output is not outputting;
When input port 1 is inactive and port 2 is inactive, no matter port 3 is active or not, defined combination output is
not outputting.