![Smartgen ACC7200 User Manual Download Page 73](http://html.mh-extra.com/html/smartgen/acc7200/acc7200_user-manual_1297470073.webp)
ACC7200 Air Compressor Controller User Manual Page 73 of 77
14.13
MTU ADEC (SAM MODULE)
Suitable for MTU engine with ADEC (ECU7) and SAM module. Engine type: Common J1939.
Table 34 ADEC (X1 Port)
Terminals of controller
ADEC (X1 port)
Remark
Auxiliary Output 1
X1 43
AUX. Output 1 is configured as “29: Fuel
Relay Output” (The configuration is factory
default).
X1 Terminal 28 connected to negative of
battery.
Auxiliary Output 2
X1 37
AUX. Output 2 is configured as “28:
Starting Relay Output” (The configuration
is factory default).
X1 Terminal 22 connected to negative of
battery.
Table 35 SAM (X23 Port)
Terminals of controller
SAM (X23 port)
Remark
-
X23 3
CAN communication shielding wire.
CAN(H)
X23 2
Using impedance 120Ω connecting line.
CAN(L)
X23 1
Using impedance 120Ω connecting line.
14.14
PERKINS
Suitable for ADEM3/ ADEM4 engine control module. Engine model is 2306, 2506, 1106, and 2806.
Engine type:
Perkins.
Table 36 Connector
Terminals of controller
Connector
Remark
Auxiliary Output 1
1, 10, 15, 33, 34
AUX. Output 1 is configured as “29: Fuel
Relay Output” (The configuration is factory
default).
Auxiliary Output 2
-
AUX. Output 2 is configured as “28:
Starting Relay Output” (The configuration
is factory default).
Connect to starter coil directly.
CAN(H)
31
Using impedance 120Ω connecting line.
CAN(L)
32
Using impedance 120Ω connecting line.