ACC7200 Air Compressor Controller User Manual Page 30 of 77
No.
Item
Range
Default
Description
or
together
and
the
purpose is to separate
starter motor and engine
as soon as possible;
8
Disconnect Speed
(0-200)%
24
Set value is the percentage
of rated speed; when
speed is above the set
value,
starter
shall
disconnect; Please refer to
the rear installation.
9
Disconnect OP
(0-1000)kPa
200
When OP is above pre-set
value,
starter
shall
disconnect. Please refer to
the rear installation.
10
Overspeed Warn
Set
(0-200.0)%
110.0
Set value is the percentage
of rated speed;
Return value and delay
value can also be set.
Return
(0-200.0)%
108.0
Delay
(0-3600)s
5
11
Overspeed
Shutdown
Set
(0-200.0)%
114.0
Set value is the percentage
of rated speed;
Delay value can also be
set.
Delay
(0-3600)s
2
12
Loss of Speed
Signal Delay
Action
(0-1)
0
0: Warning
1: Shutdown Alarm
Delay
(0-3600)s
5
Time from detecting speed
is 0 to confirm the action.
13
Battery Rated Voltage
(0-60.0)V
24.0
Provide
standard
for
battery over/under voltage
detection.
14
Battery
Overvolt
Warn
Set
(0-200)%
120
Set value is the percentage
of battery rated voltage;
Return value and delay
value can also be set.
Return
(0-200)%
115
Delay
(0-3600)s
60
15
Battery Undervolt
Warn
Set
(0-200)%
85
Return
(0-200)%
90
Delay
(0-3600)s
60
16
Charge Alt Fail
Set
(0-60.0)V
8.0
During
engine
normal
running process, when
charger D+ voltage is
below this value, controller
issues charge alt fail
warning.
Return
(0-60.0)V
10.0
Delay
(0-3600)s
10
17
Urea Level Low
Shutdown
Set
(0-100)%
10
Set value is urea level;
Return value and delay
value can also be set.
Delay
(0-3600)s
5
18
Urea Level Low Set
(0-100)%
20