ACC7200 Air Compressor Controller User Manual Page 14 of 77
Interface 4:
and
are used to change the cursor value,
is used to confirm the setting (Interface 5),
is used to return the previous interface
(Interface 2).
Interface 5:
and
are used to change the cursor value,
is used to confirm the setting,
is used to
return the previous interface (Interface 2)
Interface 6:
and
are used to change the cursor value,
is used to confirm the setting (After finishing the
last digit setting, save the data to return the Interface
3),
is used to return the previous interface
(Interface 2)
4.4
START/STOP OPERAION
4.41
START SEQUENCE
a)
Press
and start air compressor;
b)
If pre-heat time is configured, LCD displays “Pre-heat Delay xx”;
c)
After pre-heat delay is over, fuel relay outputs the pre-set fuel time before start (default: 1s), then
start relay outputs; If air compressor crank disconnect fails during “Start Time”, then fuel relay and
start relay stop outputting, and enter “Crank Rest Time”, waiting for next start;
d)
After the pre-set start attempts, if air compressor doesn't succeed to start, then controller issues