ACC7200 Air Compressor Controller User Manual Page 34 of 77
No.
Item
Range
Default
Description
1
Sensor Type
(0-4)
0
0: Not Used
1: Temperature Sensor
2: Oil Pressure Sensor
3: Level Sensor
4
:
Vibrating Sensor
2
Curve Type
Changes
according
to
sensor types.
3
Open Action
(0-2)
0
0: Warning; 1: Shutdown;
2: None
4
Display Unit
(0-1)
0
It changes according to
sensor
type,
unit
is
different
for
different
sensor.
5
Over Shutdown
Enable
(0-1)
1
When
external
sensor
value is higher than this
value, controller issues
shutdown alarm; Alarm
enable and delay value can
be set.
Set
(0-9000)
100
Delay
(0-3600)s
5
6
Under Shutdown
Enable
(0-1)
1
When
external
sensor
value is lower than this
value, controller issues
shutdown alarm; alarm
enable and delay value can
be set.
Set
(0-9000)
10
Delay
(0-3600)s
5
7
Over Warn
Enable
(0-1)
1
When
external
sensor
value is higher than this
value, controller issues
warning
alarm;
alarm
enable, return and delay
values can be set.
Set
(0-9000)
90
Return
(0-9000)
80
Delay
(0-3600)s
5
8
Under Warn
Enable
(0-1)
1
When
external
sensor
value is lower than this
value, controller issues
warning
alarm;
alarm
enable, return and delay
values can be set.
Set
(0-9000)
20
Return
(0-9000)
30
Delay
(0-3600)s
5
9
Custom Curve
When
the
custom
resistance/current/voltage
types are selected; related
curve needs to be set.
Engine Temperature Related Setting
1
Sensor Correlate Set
(0-8)
0
0: Not Used
1: Flexible Sensor 1
2: Flexible Sensor 2