ACC7200 Air Compressor Controller User Manual Page 42 of 77
No.
Item
Range
Default
Description
After overload protection,
air compressor will slow
down, and when it goes to
maint. speed, it will keep
the speed.
Alternate Configuration 2
1
Enable Choose
(0-1)
0
0: Disable 1: Enable
2
Engine Rated Speed
(0-6000) r/min
2200
When this is enabled, if
input is configured to “Alt
Config. 2 Active”, and if
input is active, speed shall
be adjusted according to
alternate
configuration
settings after load.
3
Engine Idle Speed
(0-100.0)%
64.0
4
Air Com. Onload Speed
(0-100.0)%
64.0
5
Engine Unload Speed
(0-100.0)%
70.0
6
Air Com. Target Pressure
(0-30000)kPa
700
7
Air Com. Unload Act Press
(0-30000)kPa
600
8
Onload Output Selection
(0-3)
2
0: Load Control;
1: Load Control 1
2: Load Control 2
3: Load Control 3
9
Overload Maint. Speed
(0-100.0)%
70.0
Alt Config. 2 Rated Speed
percentage;
After overload protection,
air compressor will slow
down, and when it goes to
maint. speed, it will keep
the speed.
Alternate Configuration 3
1
Enable Choose
(0-1)
0
0: Disable 1: Enable
2
Engine Rated Speed
(0-6000) r/min
2200
When this is enabled, if
input is configured to “Alt
Config. 3 Active”, and if
input is active, speed shall
be adjusted according to
alternate
configuration
settings after load.
3
Engine Idle Speed
(0-100.0)%
64.0
4
Air Com. Onload Speed
(0-100.0)%
64.0
5
Engine Unload Speed
(0-100.0)%
70.0
6
Air Com. Target Pressure
(0-30000)kPa
700
7
Air Com. Unload Act Press
(0-30000)kPa
600
8
Onload Output Selection
(0-3)
3
0: Load Control;
1: Load Control 1
2: Load Control 2
3: Load Control 3
9
Overload Maint. Speed
(0-100.0)%
70.0
Alt Config. 3 Rated Speed
percentage;
After overload protection,
air compressor will slow
down, and when it goes to
maint. speed, it will keep
the speed.