E93.1601EN032.C VGH installation manual
84
cont:
4.2.1 Boiler
parameters
min.
max.
Default
unit
Access
level
Description:
Dis
play
no:
PreHeat mode
on
off off -
Installer
Set the PreHeat Eco mode
64
Prog. Input 2.
0
4
2
#
Installer
Select the function for
programmable input 2
117
Prog. Input 3.
0
2
2
#
Installer
Select the function for
programmable input 3
118
Prog. Input 7.
0
5
3
#
Installer
Select the function for
programmable input 7
122
Prog. Input RT.
0
1
1
#
Installer
Select the function for the
programmable RT input
124
Prog. Output 1.
0
10
4
#
Installer
Select the function for
programmable output 1
125
Prog. Output 2.
0
10
9
#
Installer
Select the function for
programmable output 2
126
Prog. Output 3.
0
10
6
#
Installer
Select the function for
programmable output 3
127
Prog. Output 4.
0
20
18
#
Installer
Select the function for
programmable output 4
128
Mod. Pump dT
9
(5)
72
(40)
36
(20)
°F
(°C)
Installer
Set the modulating pump
target delta temperature
133
Mod. Pump Start Time
0
255
120
sec.
Installer
Set the modulating pump
start up time
134
Mod. Pump Type
wilo
Installer
Set the modulating pump
model
135
Mod. Pump Mode
20
100
mod
o/f or
mod.
Installer
Set the modulating pump
mode
136
Mod. Pump Min Pwr
30
%
Installer
Set the modulating pump
minimum duty cycle
137
Appliance Type 50
55
50
#
Installer
Set the appliance type 138
Dair active
0
1
yes
Yes/
No
Installer
Enable/disable the De-Air
function
139
Anti Legionella Day
mon
sun
Sunday
Installer
Select the day for the anti-
legionella cycle
107
Anti Legionella Hour
0
23
0
hrs.
Installer
Select the time for the anti-
legionella cycle
108
4.2.2 Module Cascade
Settings
min.
max. Default
unit
Access
level
Description:
Dis
play
no:
Burner Address
Stand
alone
Installer
Set the cascade burner
address
184
Permit Emergency Mode
Yes
Yes/
No
Installer
Enable/disable the cascade
emergency mode
72
Emergency Setpoint
68
(20)
194
(90)
158
(70)
°F
(°C)
Installer
Set the emergency mode
setpoint
74
Delay Per Start Next Mod. 0
1275 200
sec.
Installer
Set the delay time before
the next module is started
75
Delay Per Stop Next Mod. 0
1275 180
sec.
Installer
Set the delay time before
the next module is stopped
76
Delay Quick Start Next
0
1275 50
sec.
Installer
Set the fast delay time
before the next module is
started
142
Delay Quick Stop Next
0
1275 30
sec.
Installer
Set the fast delay time
before the next module is
stopped
143
Hyst. Down Start Module
0
(0)
72
(40)
9
(5)
°F
(°C)
Installer
Set the hysteresis down
after which a module is
started
77
Summary of Contents for VGH-299-CH
Page 6: ...E93 1601EN032 C VGH installation manual 6 1 SAFETY GUIDELINES ...
Page 59: ...E93 1601EN032 C VGH installation manual 59 Ladder Logic Diagram Figure 11 3 ...
Page 60: ...E93 1601EN032 C VGH installation manual 60 Electrical schematics Figure 11 4 ...
Page 61: ...E93 1601EN032 C VGH installation manual 61 Figure 11 5 ...
Page 123: ...E93 1601EN032 C VGH installation manual 123 22 SPARE PARTS Figure 22 1 ...
Page 124: ...E93 1601EN032 C VGH installation manual 124 Figure 22 2 ...
Page 127: ...E93 1601EN032 C VGH installation manual 127 ...